Q.60 A single-phase transformer of rating 25kVA, supplies a 12kW load at power factor of 0.6 lagging.The additional load at unity power factor in kW (round off to two decimal places) that may be added before this transformer exceeds its rated kVA is __________.
Answer:(7.2)
Explanation: