Maximum demand calculator:
Enter the Peak Operating Load for 30 minutes’ block and power factor between 0 to 1, then press the calculate button to get the Maximum demand in kVA.
Maximum demand Calculation:
The maximum demand in kVA is nothing but a peak operating load (maximum load) in kW of the consumer for the specific interval divided by the operating power factor. The interval will be defined by your electricity provider. Hence, the maximum demand formula can be written as,
Maximum demand in kVA = Peak Load in kW / Power factor
If you know load factor and connected load means
Maximum Demand= Connected Load x Load Factor / Power Factor.
In India, Maharashtra state MSEB has 30 minutes’ block, which means, the continuous peak demand will be calculated within any 30 minutes. Gujarat has 15 minutes and 30 minutes’ block.
Note that the maximum demand will be calculated from kVA only.
Example:
Now you are running 5 numbers of 5.5 kW motor @ 90% of the load with 0.86 pf. Calculate the maximum demand.
Peak Load = 5 * 5.5 * 0.9 = 24.75kW
Maximum demand = Peak load / power factor
=24.75 / 0.86
= 28.77kVA
Look at the table of India’s all-state maximum demand charges per kVA. The penalty is applicable when the maximum demand exceeds the contracted demands.
Maximum Demand Charges | ||
State | MD Charges (INR Per kVA) | Penalty (%) |
Telangana | 390 | 150 |
Tamilnadu | 350 | 130 |
Kerala | 300 | 130 |
Karnataka | 275 | 200 |
Maharashtra | 150 | 150 |
Pondicherry | 300 | 200 |
Andhra Pradesh | 475 | 150 |
Assam | 375 | 120 |
Bihar | 330 | NA |
Chandigarh | 300 | 120 |
Chhattisgarh | 350 | 115 |
Delhi | 350 | 130 |
Goa | 200 | NA |
Gujarat | 360 | 200 |
Haryana | 750 | NA |
Himachal Pradesh | 400 | NA |
Jammu and Kashmir | 135 | NA |
Jharkhand | 400 | NA |
Madhya Pradesh | 310 | 120 |
Odisha | 250 | NA |
Punjab | 179 | 250/kVA |
Rajasthan | 270 | NA |
Sikkim | 555 | NA |
Uttar Pradesh | 340 | NA |
Uttarakhand | 360 | NA |
West Bengal | 384 | 200 |
NA- Not Available |
How to reduce Maximum demand:?
- Maintain power factor near to unity. Since the power factor is inversely proportional to the maximum demand. Hence by increasing power factor, the maximum demand will be reduced.
- Avoid bulk switch On load. Keep scheduling the load.
- Install Speed driver.
- Optimize the single load. Example, you have two motors which is operated at 50% of load, here you can cut off one motor and shift the load to a single motor. By the way, we can reduce 30% of the load.
If Exceed the maximum demand, what effect will be happen in EB side.
They charge additionally by 50% of the rate for which exceeding the nominal.
Sorry sir, How to they find in EB side.
Yes, they find from the EB side energy meter (main meter).